 Question by MJ Goodsell posted 16 May 2006
 shielded cat5e termination
Can some one please tel me the specs on terminating Cat5e data cable. I will be terminating both ends on Leviton Cat5e inserts, one end is in telco closet, other at users desk. Is it correct only terminating one end of the drain (shield)? Also what do I connect the drain to? Thank you, MJ
icon
 Answer by Joseph Golan posted 16 May 2006
Dear MJ,

While it is unusual to use shielded cable with unshielded jacks, it can be done.

First, here is a link to a PDF file on termination category 5 jacks from Leviton:
http://www.levitonvoicedata.com/support/documents/instructionsheets/41108xx5.pdf

Typically you would only connect the shield one end (telco closet) when using shielded cable with non-shielded jacks. Connect the drain wire of the shield to a good earth ground in the rack, extending the wire is needed.

Sincerely,
Joseph Golan, RCDD

Click here to see the expert's profile
Back to the current page of questions | Back to all the questions
Back to Cabling-Design.com HELPDESK | Ask your question
Residential Cabling Guide

Home Cabling Guide

Finally, an instantly downloadable book that saves you thousands in home improvement dollars! Enjoy living in 21st century technology-advanced home while increasing its selling value and competitive advantage on the real estate market. Whether your cabling is for home office or high-tech leisure, you can wire your home yourself or learn "wirish" to speak with your cabling contractors in their language!