 Question by chfis hautman posted 25 Jan 2005
 Plenum Cable
I am running cable above a suspended ceiling and inside non load bearing walls. Do I need to use plenum cable?
No cable is run inside any air ducts.
Please advices
icon
 Answer by Joseph Golan posted 28 Jan 2005
Dear chfis,

Plenum rated cable must be used if the space you are running through is an air-plenum, typically found in commercial space as the return path for the air handling. It is not advised to run cable in actual air supply or return ducts. If the office have duct return systems then typically the void above the hung ceiling is not an air plenum, cjeck with the building owner or a mechanical engineer before proceeding.

Sincerely,
Joseph Golan, RCDD

Click here to see the expert's profile
Back to the current page of questions | Back to all the questions
Back to Cabling-Design.com HELPDESK | Ask your question
Residential Cabling Guide

Home Cabling Guide

Finally, an instantly downloadable book that saves you thousands in home improvement dollars! Enjoy living in 21st century technology-advanced home while increasing its selling value and competitive advantage on the real estate market. Whether your cabling is for home office or high-tech leisure, you can wire your home yourself or learn "wirish" to speak with your cabling contractors in their language!